Parameter Groups
‑215‑
F6-28
Electromagnetic shorting time upon stop
Address:
0xF61C
Min.:
0
Unit:
s
Max.: 100 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
0.0s to 100.0s
Description
F6-29
Electromagnetic shorting voltage reserve
Address:
0xF61D
Min.:
20
Unit:
V
Max.: 100 Data type: UInt16
Default:
20
Change:
At stop
Value Range:
20.0 V to 100.0 V
Description
F6-30
Trial current for synchronous motor speed tracking
Address:
0xF61E
Min.:
5
Unit:
Max.: 50 Data type: UInt16
Default:
10
Change:
At stop
Value Range:
5.0 to 50.0
Description
F6-31
Minimum tracking frequency for synchronous motor speed tracking
Address:
0xF61F
Min.:
0
Unit:
Max.: 100 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
0.0100.0
Description
F6-32
Angle compensation for synchronous motor speed tracking
Address:
0xF620