Parameter Groups
‑220‑
Description
If a parameter needs to be displayed during running, set its corresponding bit to
1. After converting this binary number to a hexadecimal number, set it in F7‑04
F7-05
LED stop display parameter
Address:
0xF705
Min.:
0
Unit:
‑
Max.: 0xFFFF Data type: UInt16
Default:
0x33
Change: In real time
Value Range:
Bit00: Frequency reference (Hz)
Bit01: Bus voltage (V)
Bit02: DI state
Bit03: DO state
Bit04: AI1 voltage (V)
Bit05: AI2 voltage (V)
Bit06: AI3 voltage (V)
Bit07: Count value
Bit08: Length value
Bit09: PLC stage
Bit10: Load speed display
Bit11: PID reference
Bit12: Pulse input frequency (kHz)
Bit13: Roll diameter (mm)
Bit14: Tension (N)
Description
If a parameter needs to be displayed when the AC drive stops, set its
corresponding bit to 1. After converting this binary number to a hexadecimal
number, set it in F7‑05.
F7-06
Load speed display coefficient
Address:
0xF706
Min.:
0
Unit:
‑
Max.: 6.5 Data type: UInt16
Default:
1
Change: In real time
Value Range:
0.0000 to 6.5
Description
This parameter defines the ratio of the actual speed with load to motor speed.