Parameter Groups
‑229‑
Value Range:
0–65000 h
Description
This parameter is used to set the accumulative running time threshold of the AC
drive. When F7‑09 (Accumulative running time) exceeds F8‑20 (Accumulative
running time threshold), the DO outputs an active signal.
F8-18
Protection upon start
Address:
0xF812
Min.:
0
Unit:
‑
Max.: 1 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0: Disabled
1: Enabled
Description
The AC drive is equipped with the startup protection function to prevent the
motor from responding to commands upon unexpected power‑on or fault reset.
F8-19
Frequency detection value (FDT1)
Address:
0xF813
Min.:
0
Unit:
Hz
Max.: F0‑10 Data type: UInt16
Default:
50
Change: In real time
Value Range:
0.00 Hz to value of F0‑10
Description
When the running frequency is higher than the frequency detection value (FDT1),
the DO outputs an active signal. When the running frequency is lower than the
result of frequency detection value (FDT1) minus frequency detection hysteresis
(FDT1), the DO outputs an inactive signal. The valid range is from 0.00 Hz to F0‑10
(Maximum frequency).
F8-20
Frequency detection hysteresis (FDT1)
Address:
0xF814
Min.:
0
Unit:
%
Max.: 100 Data type: UInt16
Default:
5
Change: In real time
Value Range:
0.0% to 100.0%