Parameter Groups
‑359‑
A6-10
Curve 5 inflexion 1 input
Address:
0xA60A
Min.:
A6‑08
Unit:
V
Max.: A6‑12 Data type: Int16
Default:
‑3
Change: In real time
Value Range:
A6‑08 to A6‑12
Description
This parameter defines the x axis of inflexion 1 on AI curve 5, that is, the analog
input voltage or current at inflexion 1.
A6-11
Corresponding setting of curve 5 inflexion 1 input
Address:
0xA60B
Min.:
‑100
Unit:
%
Max.: 100 Data type: Int16
Default:
‑30
Change: In real time
Value Range:
‑100.0% to +100.0%
Description
This parameter defines the y axis of inflexion 1 on AI curve 5, that is, the setting
value at inflexion 1.
A6-12
Curve 5 inflexion 2 input
Address:
0xA60C
Min.:
A6‑10
Unit:
V
Max.: A6‑14 Data type: Int16
Default:
3
Change: In real time
Value Range:
A6‑10 to A6‑14
Description
This parameter defines the x axis of inflexion 2 on AI curve 5, that is, the analog
input voltage or current at inflexion 2.
A6-13
Corresponding setting of curve 5 inflexion 2 input
Address:
0xA60D
Min.:
‑100
Unit:
%
Max.: 100 Data type: Int16
Default:
30
Change: In real time
Value Range:
‑100.0% to +100.0%