Parameter Groups
‑387‑
Description
When analog voltage correction is carried out on the AO1 terminal, a correction
curve is formed through two points. Each point corresponds to a target voltage
and a measured voltage. The target voltage is the expected output voltage, and
the measured voltage is the output voltage actually measured.
AC-15
AO1 target voltage 2
Address:
0xAC0F
Min.:
‑10
Unit:
V
Max.: 10 Data type: Int16
Default:
8
Change: In real time
Value Range:
‑10.000 V to +10.000 V
Description
When analog voltage correction is carried out on the AO1 terminal, a correction
curve is formed through two points. Each point corresponds to a target voltage
and a measured voltage. The target voltage is the expected output voltage, and
the measured voltage is the output voltage actually measured.
AC-16
AO2 measured voltage 1
Address:
0xAC10
Min.:
‑10
Unit:
V
Max.: 10 Data type: Int16
Default:
2
Change: In real time
Value Range:
‑10.000 V to +10.000 V
Description
When analog voltage correction is carried out on the AO2 terminal, a correction
curve is formed through two points, and each point corresponds
to a target voltage and a measured voltage. The target voltage is the expected
output voltage, and the measured voltage is the output voltage actually
measured.
AC-17
AO2 target voltage 1
Address:
0xAC11
Min.:
‑10
Unit:
V
Max.: 10 Data type: Int16
Default:
2
Change: In real time
Value Range:
‑10.000 V to +10.000 V
Description