Parameter Groups
‑389‑
Description
When PT100 analog voltage correction is carried out on AI3, a correction curve is
formed through two points. Each point corresponds to a measured voltage and a
displayed voltage. The measured voltage is the voltage measured using a meter,
and the displayed voltage is the PTC voltage before correction (U0‑47).
AC-21
PT100 displayed voltage 1
Address:
0xAC15
Min.:
0
Unit:
V
Max.: 3.3 Data type: Int16
Default:
0.44
Change: In real time
Value Range:
0.000 V to 3.3 V
Description
When PT100 analog voltage correction is carried out on AI3, a correction curve is
formed through two points. Each point corresponds to a measured voltage and a
displayed voltage. The measured voltage is the voltage measured using a meter,
and the displayed voltage is the PTC voltage before correction (U0‑47).
AC-22
PT100 measured voltage 2
Address:
0xAC16
Min.:
0
Unit:
V
Max.: 3.3 Data type: Int16
Default:
2.16
Change: In real time
Value Range:
0.000 V to 3.3 V
Description
When PT100 analog voltage correction is carried out on AI3, a correction curve is
formed through two points. Each point corresponds to a measured voltage and a
displayed voltage. The measured voltage is the voltage measured using a meter,
and the displayed voltage is the PTC voltage before correction (U0‑47).
AC-23
PT100 displayed voltage 2
Address:
0xAC17
Min.:
0
Unit:
V
Max.: 3.3 Data type: Int16
Default:
2.16
Change: In real time
Value Range:
0.000 V to 3.3 V