Parameter Groups
418
Value Range:
0: Disabled
1: Enabled
Description
This parameter takes effect only when B0‑07 is set to 1.
When the winding diameter is calculated by thickness accumulation, the winding
diameter increases/decreases with the number of revolutions of the reel. At this
time, this parameter can be set to 1 to avoid the cumulative error caused by the
failure of winding diameter calculation during pre‑driving. You can set this
parameter according to the actual operations.
B0-26
Tension frequency limit
Address:
0xB01A
Min.:
0
Unit:
%
Max.: 100 Data type: UInt16
Default:
50
Change: In real time
Value Range:
0.0% to 100.0%
Description
Limit percentage (a percentage of the linear speed synchronous frequency)
B0-27
Tension frequency limit offset
Address:
0xB01B
Min.:
0
Unit:
Hz
Max.: 100 Data type: UInt16
Default:
5
Change: In real time
Value Range:
0.00 Hz to 100.00 Hz
Description
Limit offset (fixed frequency)
B0-28
Tension frequency limit
Address:
0xB01C
Min.:
0
Unit:
Max.: 1 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0: Disabled
1: Enabled
Description
B0‑00=2: B0‑28 is used to enable the speed closed‑loop PID adjustment limit.