Parameter Groups
‑419‑
B0‑00=0: Limit the tension frequency according to B0‑26 and B0‑27 (limited by
upper limit frequency)
B0‑00=1: Limit the tension frequency to the fixed frequency set by B0‑27.
In speed mode, when open‑loop reference and closed‑loop adjustment are used,
closed‑loop adjustment must be limited to avoid system shock and ensure system
stability. For this reason, in the speed closed‑loop adjustment, based on the
synchronization frequency (the running frequency that the rewinder matches the
current linear speed) and the speed closed‑loop limiter offset, the closed‑loop
adjustment frequency upper limit can be obtained according to the following
formula by default (B0‑28=0).
Closed‑loop adjustment frequency upper limit = synchronous frequency x B0‑26 +
B0‑27
When B0‑28 is set to 1, the upper limit of the closed‑loop adjustment frequency is
the fixed frequency B0‑27.
B0‑00≠2: B0‑28 is used to limit the speed limit (effective for winding).
0: No limit (limited by the upper limit frequency)
1: Limit the frequency according to B0‑26 and B0‑27.
In the torque mode, by default (B0‑28=0), the upper limit of the winding frequency
is not limited. To prevent material breaking and runaway, the above parameters
can be set to limit the upper limit of the winding frequency. When B0‑28 is set to
1, the upper limit of the winding frequency is obtained according to the following
formula based on the synchronization frequency (the running frequency that the
rewinder matches the current linear speed) and the frequency limit offset.
Winding frequency upper limit = Synchronous frequency x (1 + B0‑26) + B0‑27
B0-29
Pulses per revolution
Address:
0xB01D
Min.:
1
Unit:
‑
Max.: 60000 Data type: UInt16
Default:
1
Change: In real time
Value Range:
1 to 60000
Description
This parameter specifies the number of pulses per revolution of the reel.
B0-30
Revolutions per layer
Address:
0xB01E
Min.:
1
Unit:
‑
Max.: 10000 Data type: UInt16
Default:
1
Change: In real time
Value Range: