Parameter List
‑41‑
Parame
ter
Address Name Value Range Default Unit Change
Method
Page
F9‑44 0xF92C Running time
upon 1st fault
0.0 to 6553.5 0 ‑ Unchangea
ble
"
F9‑44
"
on
page 252
F9‑45 0xF92D IGBT temperature
upon 1st fault
‑20℃ to +120℃ 0 °C Unchangea
ble
"
F9‑45
"
on
page 253
F9‑46 0xF92E Fault subcode
upon 1st fault
0 to 65535 0 ‑ Unchangea
ble
"
F9‑46
"
on
page 253
F9‑47 0xF92F Fault protection
action selection 0
Ones (position): Value of E02,
E03, and E04
0: Coast to stop
2: Restart upon fault
Tens (position): Value of E05,
E06, and E07
0: Coast to stop
2: Restart upon fault
0 ‑ At stop "
F9‑47
"
on
page 253
Contin
ued
Contin
ued
Continued Hundreds (position): Value of
E08
0: Coast to stop
Thousands (position): Value of
E09
0: Coast to stop
2: Restart upon fault
Ten thousands (position):
Value of E10
0: Coast to stop
2: Restart upon fault
Contin
ued
Contin
ued
Continued Continued
F9‑48 0xF930 Fault protection
action selection 1
Ones (position): Value of E11
0: Coast to stop
1: Decelerate to stop
2: Restart upon fault
4: Warning
5: Canceled
Tens (position): Value of E12
0: Coast to stop
1: Decelerate to stop
2: Restart upon fault
4: Warning
5: Canceled
0 ‑ At stop "
F9‑48
"
on
page 254