Parameter List
46
Parame
ter
Address Name Value Range Default Unit Change
Method
Page
F9‑59 0xF93B Selection of power
dip ride‑through
action
0: Disabled
1: Busbar voltage constant
control
2: Decelerate to stop
3: Voltage dip depression
0 At stop "
F9‑59
"
on
page 263
F9‑60 0xF93C Voltage to
determine the
pause of power
dip ride‑through
80% to 100% 85 % In real time "
F9‑60
"
on
page 263
F9‑61 0xF93D Duration for
judging voltage
recovery from
power dip ride‑
through
0.0100.0s 0.5 s In real time "
F9‑61
"
on
page 264
F9‑62 0xF93E Threshold for
enabling power
dip ride‑through
60% to 100% 80 % In real time "
F9‑62
"
on
page 264
F9‑63 0xF93F Runaway
protection time in
FVC mode
0 to 10000 0 At stop "
F9‑63
"
on
page 264
F9‑64 0xF940 Load loss
detection level
0.0% to 100.0% 10 % In real time "
F9‑64
"
on
page 265
F9‑65 0xF941 Load loss
detection time
0.0s60.0s 1 s In real time "
F9‑65
"
on
page 265
F9‑66 0xF942 Voltage dip
suppression time
0.0s to 600.0s 0 s Unchangea
ble
"
F9‑66
"
on
page 265
F9‑67 0xF943 Overspeed
threshold
0.0% to 50.0% 5 % In real time "
F9‑67
"
on
page 266
F9‑68 0xF944 Overspeed
detection time
0.060.0 1 In real time "
F9‑68
"
on
page 266
F9‑69 0xF945 Excessive speed
deviation
threshold
0.0% to 50.0% 20 % In real time "
F9‑69
"
on
page 266
F9‑70 0xF946 Detection time of
excessive speed
deviation
0.0s to 60.0s 5 s In real time "
F9‑70
"
on
page 267
F9‑71 0xF947 Power dip ride‑
through gain
0 to 100 40 In real time "
F9‑71
"
on
page 267
F9‑72 0xF948 Power dip ride‑
through integral
0 to 100 30 In real time "
F9‑72
"
on
page 267
F9‑73 0xF949 Deceleration time
of power dip ride‑
through
0.0s to 300.0s 20 s In real time "
F9‑73
"
on
page 268