Parameter List
‑45‑
Parame
ter
Address Name Value Range Default Unit Change
Method
Page
F9‑53 0xF935 Fault protection
action selection 6
Ones (position): Value of E45
0: Coast to stop
1: Decelerate to stop
4: Warning
5: Canceled
Tens (position): Value of E60
0: Coast to stop
1: Decelerate to stop
4: Warning
5: Canceled
0 At stop "
F9‑53
"
on
page 260
Contin
ued
Contin
ued
Continued Hundreds (position): Value of
E61
0: Coast to stop
1: Decelerate to stop
4: Warning
5: Canceled
Thousands (position): Value of
E62
0: Coast to stop
5: Canceled
Ten thousands (position):
Reserved
5: Canceled
Contin
ued
Contin
ued
Continued Continued
F9‑54 0xF936 Frequency
selection for
continuing to run
upon fault
0: Current running frequency
1: Frequency reference
2: Frequency upper limit
3: Frequency lower limit
4: Backup frequency upon
abnormality
1 In real time "
F9‑54
"
on
page 261
F9‑55 0xF937 Backup frequency
reference upon
abnormality
0.0% to 100.0% 100 % In real time "
F9‑55
"
on
page 261
F9‑56 0xF938 Motor temperature
sensor type
0: No sensor (AI3 input)
1: PT100
2: PT1000
3: KTY84
4: PTC130
0 In real time "
F9‑56
"
on
page 262
F9‑57 0xF939 Motor
overtemperature
protection
threshold
0℃ to 200℃ 110 °C In real time "
F9‑57
"
on
page 262
F9‑58 0xF93A Motor
overtemperature
pre‑warning
threshold
0℃ to 200℃ 90 °C In real time "
F9‑58
"
on
page 262