Parameter List
56
Parame
ter
Address Name Value Range Default Unit Change
Method
Page
FC‑49 0xFC31 Acceleration/
Deceleration time
of PLC reference
15
0: Group 1 acceleration/
deceleration time (F0‑17 and
F0‑18)
1: Group 2 acceleration/
deceleration time (F8‑03 and
F8‑04)
2: Group 3 acceleration/
deceleration time (F8‑05 and
F8‑06)
3: Group 4 acceleration/
deceleration time (F8‑07 and
F8‑08)
0 In real time "
FC‑49
"
on
page 300
FC‑50 0xFC32 PLC running time
unit
0: s (second)
1: h (hour)
0 In real time "
FC‑50
"
on
page 301
FC‑51 0xFC33 Multi‑reference 0
source
0: Multi‑reference 0 (FC‑00)
1: AI1
2: AI2
3: AI3
4: Pulse reference (DI5)
5: PID
6: Preset frequency (F0‑08 that
can be changed by pressing
UP or DOWN key)
0 In real time "
FC‑51
"
on
page 301
FD‑00 0xFD00 Baud rate 0: 300 bit/s
1: 600 bit/s
2: 1200 bit/s
3: 2400 bit/s
4: 4800 bit/s
5: 9600 bit/s
6: 19200 bit/s
7: 38400 bit/s
8: 57600 bit/s
9: 115200 bit/s
5 In real time "
FD‑00
"
on
page 302
FD‑01 0xFD01 Modbus data
format
0: No check (8‑N‑2) 1: Even
parity check (8‑E‑1)
2: Odd parity check (8‑O‑1)
3: No check (8‑N‑1)
0 In real time "
FD‑01
"
on
page 302
FD‑02 0xFD02 Local address 1 to 247 1 In real time "
FD‑02
"
on
page 302
FD‑03 0xFD03 Response delay 020 ms 2 ms In real time "
FD‑03
"
on
page 303
FD‑04 0xFD04 Modbus
communication
timeout time
0.0s to 60.0s 0 s In real time "
FD‑04
"
on
page 303
FD‑06 0xFD06 Communication
fault reset
0: Disabled
1: Enabled
1 At stop "
FD‑06
"
on
page 304