Goodrive300-01A-RT series integrated machine Function description
-66-
Description Default Modify
0: Invalid
1: Automatic sleep mode
2: Manual sleep mode
Note: When automatic sleep function is valid
and unloading conditions are fulfilled, the
VFD decelerates to P18.12 [no-load running
frequency], and then, if discharge pressure is
larger than P18.06 [loading pressure] during
the time set by P18.13 [no-load delay], the
VFD will decelerate to P01.15 [stop speed]
and then coast to stop to enter sleep stage. If
the discharge pressure is less than loading
Time
Present
pressure
P18.05
P18.07
P18.06
0
Time
Present running frequency
P00.04
P18.12
0
P01.15
Sleep trigger
Sleep stop
Automatic sleep mode
0
Load
1
P18.13
Enabling
signal
Manual sleep
mode
Time
Time
Present running
frequency
P00.04
P18.12
0
P01.15
Sleep trigger Sleep stop
Manual sleep
command
Load
0
0
1
1
P18.13