Goodrive300-01A-RT series integrated machine Function description
-68-
air compressor runs stably. During
load-carrying running, the motor speed is
controlled by pressure PID, and the system
keeps the discharge pressure constant via
adjusting master speed.
Setting range: 0.00–P18.04
Starting temperature of
the fan
When the machine head temperature is
higher than P18.08, the fan starts.
When the machine head temperature is
lower than P18.09, the fan stops.
Setting range: -20–150
Stopping temperature
of the fan
Lower-limit frequency
at load-carrying
running
P18.12–P00.04 (upper limit of running
frequency)
During the pressure PID regulating, the
allowed min. working frequency is P18.11.
No-load running
frequency
P01.15–P18.11 (lower-limit frequency of
load-carrying running)
The output working frequency allowed during
no-load of air compressor.
When sleep function is valid, after unloading,
the VFD runs at no-load frequency in the
time set by P18.13, and then enters sleep
state.
When air consumption quantity is small,
users can enable sleep function; if sleep
function is valid, it is necessary to lower
down P18.13 to make the device enter sleep
state quicker.
Setting range: 0–3600s
After the stopping command becomes valid,
the VFD will first run at no-load frequency in
the time set by P18.14, and then stops.
Setting range: 0–3600s
Loading operation is available only after the
motor runs at no-load frequency in the time
set by P18.15.
Setting range: 0–3600s