138
Error no. Type Message text Notes/solution
F212 Time/Date The time and date still need to be set.
Parameter Setting
System Control
Time/Date
F229 Info Wrong Passcode
An incorrect passcode was entered. Passcode Entry, p. 48
F236 HART not Available,
Current too Low
HART is not available with currents smaller than 4 mA: Set current output I1
to 4-20mA.
Parameter Setting
Inputs and Outputs
Current Outputs
Current Output I1
Output
Current Output/Relay Contacts
Error no. Type Message text Notes/solution
B070 Current I1 Span Current output 1: The selected span is too small/too big:
Parameter Setting
Inputs and Outputs
Current Outputs
Current Output I1
Check start/end.
B071 Current I1 < 0/4 mA Current output 1: The current is below the permissible limit.
B072 Current I1 > 20 mA Current output 1: The current is above the permissible limit.
B073 Current I1 Load Error Current output 1: The current loop has been interrupted (open circuit) or
the load is too high: Deactivate or short-circuit unused current outputs.
B074 Current I1 Parameter Current output 1: Check the configuration.
B075 Current I2 Span Current output 2: The selected span is too small/too big:
Parameter Setting
Inputs and Outputs
Current Outputs
Current Output I2
Check start/end.
B076 Current I2 < 0/4 mA Current output 2: The current is below the permissible limit.
B077 Current I2 > 20 mA Current output 2: The current is above the permissible limit.
B078 Current I2 Load Error Current output 2: The current loop has been interrupted (open circuit) or
the load is too high: Deactivate or short-circuit unused current outputs.
B079 Current I2 Parameter Current output 2: Check the configuration.
B080 Current I3 Span Current output 3: The selected span is too small/too big:
Parameter Setting
Inputs and Outputs
Current Outputs
Current Output I3
Check start/end.
B081 Current I3 < 0/4 mA Current output 3: The current is below the permissible limit.
B082 Current I3 > 20 mA Current output 3: The current is above the permissible limit.
B083 Current I3 Load Error Current output 3: The current loop has been interrupted (open circuit) or
the load is too high: Deactivate or short-circuit unused current outputs.
B084 Current I3 Parameter Current output 3: Check the configuration.
B085 Current I4 Span Current output 4: The selected span is too small/too big:
Parameter Setting
Inputs and Outputs
Current Outputs
Current Output I4
Check start/end.
B086 Current I4 < 0/4 mA Current output 4: The current is below the permissible limit.
B087 Current I4 > 20mA Current output 4: The current is above the permissible limit.
B088 Current I4 Load Error Current output 4: The current loop has been interrupted (open circuit) or
the load is too high: Deactivate or short-circuit unused current outputs.
B089 Current I4 Parameter Current output 4: Check the configuration.