June 2018
122 Legrand PDU User Guide
State Description
below lower warning Lower Critical threshold <= "R" < Lower
Warning threshold
above upper warning Upper Warning threshold < "R" <= Upper
Critical threshold
above upper critical Upper Critical threshold < "R"
alarmed The state sensor enters the abnormal state.
unavailable
The communication with the managed
sensor is lost.
-- OR --
DPX2, DPX3 or DX sensor packages are
upgrading their sensor firmware.
Note that for a contact closure sensor, the normal state depends on the normal setting you have configured.
Refer to the Environmental Sensors and Actuators Guide (or Online Help) for detailed information, which is
available on Raritan's Support page (http://www.raritan.com/support/).
Manag
ed
actuator states:
State Description
on The actuator is turned on.
off The actuator is turned off.
unavailable
The communication with the managed
actuator is lost.
-- OR --
DX sensor packages are upgrading their
sensor firmware.
Unmanaged sensor/actuator states:
State Description
unmanaged Sensors or actuators are physically connected
to the Legrand PDU but not managed yet.
Note: Unmanaged sensors or actuators will disappear from the web interface after they are no longer
physically connected to the Legrand PDU. To manage a sensor/actuator, go to Peripherals (on page 116).
Finding the Sensor's Serial Number
A DPX environmental sensor package includes a serial number tag on the sensor cable.