Legrand PDU User Guide 263
2. In the SNMP Agent, make sure the Enable SNMP v1/v2c checkbox is selected.
3. In the SNMP Notifications section, make sure the Enable SNMP Notifications checkbox is selected.
4. Select SNMPv2c Trap or SNMPv2c Inform as the notification type.
5. Type values in the following fields.
Field Description
Timeout The interval of time, in seconds, after which a new
inform communication is resent if the first is not
received.
For example, resend a new inform
communication once every 3 seconds.
Number of Retries The number of times you want to resend the inform
communication if it fails.
For example, inform communications are resent
up to 5 times when the initial communication
fails.
Host The IP address of the device(s) you want to
access. This is the address to which notifications
are sent by the SNMP agent.
You can specify up to 3 SNMP destinations.
Port The port number used to access the device(s).
Community The SNMP community string to access the
device(s). The community is the group
representing the Legrand PDU and all SNMP
management stations.
6. Click Save.
SNMPv3 Notifications
1. Choose Device Settings > Network Services > SNMP.
2. In the SNMP Agent, make sure the Enable SNMP v1/v2c checkbox is selected.