June 2018
288 Legrand PDU User Guide
Load Shedding Settings
This section applies to outlet-switching capable models only.
This command shows the load shedding settings.
# show loadshedding
Displayed information:
The load shedding state is displayed along with non-critical outlets.
Note: The load shedding mode is associated with critical and non-critical outlets. To specify critical and
non-critical outlets through CLI, see Specifying Non-Critical Outlets (on page 296).
Serial Port Settings
This command shows the baud rate setting of the serial port labeled CONSOLE on the Legrand PDU.
# show serial
EnergyWise Settings
This command shows the Legrand PDU device's current configuration for Cisco
®
EnergyWise.
# show energywise
Event Log
The command used to show the event log begins with show eventlog. You can add either the limit or class
parameters or both to show specific events.
Show the last 30 entries:
# show eventlog
Show a specific number of last entries in the event log:
# show eventlog limit <n>
Show a specific type of events only:
# show eventlog class <event_type>
Show a specific number of last entries associated with a specific type of events only:
# show eventlog limit <n> class <event_type>
Variables:
<n> is one of the options: all or a number.
Option Description
all Displays all entries in the event log.