296 Legrand PDU User Guide
Setting the Inrush Guard Delay Time
This section applies to outlet-switching capable models only.
This command sets the inrush guard delay.
config:# pdu inrushGuardDelay <timing>
Variables:
<timing> is a delay time between 100 and 100000 milliseconds.
Setting the Outlet Initialization Delay
This section applies to outlet-switching capable models only.
This command determines the outlet initialization delay timing on device startup. See PDU (on page 94) for
information on outlet initialization delay.
config:# pdu outletInitializationDelayOnDeviceStartup <timing>
Variables:
<timing> is a delay time between 1 and 3600 seconds.
Specifying Non-Critical Outlets
This section applies to outlet-switching capable models only.
This command determines critical and non-critical outlets. It is associated with the load shedding mode. See
Load Shedding Mode (on page 105).
config:# pdu nonCriticalOutlets <outlets1>:false;<outlets2>:true
Separate outlet numbe
rs and their settings with a colon. Separate each "false" and "true" setting with a
semicolon.
Variables:
<outlets1> is one or multiple outlet numbers to be set as critical outlets. Use commas to separate outlet
numbers.
Use a dash for a range of consecutive outlets. For example, 3-8 represents outlets 3 to 8.
<outlets2> is one or multiple outlet numbers to be set as NON-critical outlets. Use commas to separate
outlet numbers.
Use a dash for a range of consecutive outlets. For example, 3-8 represents outlets 3 to 8.