Legrand PDU User Guide 297
Enabling or Disabling Data Logging
This command enables or disables the data logging feature.
config:# pdu dataRetrieval <option>
Variables:
<option> is one of the options: enable or disable.
Option Description
enable Enables the data logging feature.
disable Disables the data logging feature.
For more information, see Setting Data Logging (on page 219).
Setting Data Logging Measurements Per Entry
This command defines the number of measurements accumulated per log entry.
config:# pdu measurementsPerLogEntry <number>
Variables:
<number> is an integer between 1 and 600. The default is 60 samples per log entry.
For more information, see Setting Data Logging (on page 219).
Specifying the Device Altitude
This command specifies the altitude of your Legrand PDU above sea level (in meters). You must specify the
altitude of Legrand PDU above sea level if a Raritan's DPX differential air pressure sensor is attached. This
is because the device's altitude is associated with the altitude correction factor. See Altitude Correction
Factors (on page 480).
config:# pdu deviceAltitude <altitude>
Variabl
es:
<altitude> is
an integer between -425 and 3000 meters.
Note that the lower limit "-425" is a negative value because some locations are below the seal level.