298 Legrand PDU User Guide
Setting the Z Coordinate Format for Environmental Sensors
This command enables or disables the use of rack units for specifying the height (Z coordinate) of
environmental sensors.
config:# pdu externalSensorsZCoordinateFormat <option>
Variables:
<option> is one of the options: rackUnits or freeForm.
Option Description
rackUnits The height of the Z coordinate is measured in
standard rack units.
When this is selected, you can type a numeric
value in the rack unit to describe the Z coordinate
of any environmental sensors or actuators.
freeForm Any alphanumeric string can be used for
specifying the Z coordinate.
Note: After determining the format for the Z coordinate, you can set a value for it. See Setting the Z
Coordinate (on page 365).
Enabling or Disabling Peripheral Device Auto Management
This command enables or disables the Peripheral Device Auto Management feature.
config:# pdu peripheralDeviceAutoManagement <option>
Variables:
<option> is one of the options: enable or disable.
Option Description
enable Enables the automatic management feature for
environmental sensor packages.
disable Disables the automatic management feature for
environmental sensor packages.
For more information, see How the Automatic Management Function Works (on page 98).