June 2018
Legrand PDU User Guide 367
Configuring Environmental Sensors' Default Thresholds
You can set the default values of upper and lower thresholds, deassertion hysteresis and assertion timeout
on a sensor type basis, including temperature, humidity, air pressure and air flow sensors. The default
thresholds automatically apply to all environmental sensors that are newly detected or added.
A default threshold configuration command begins with defaultThresholds.
You can configure various default threshold settings for the same sensor type at a time by combining
multiple commands. See Multi-Command Syntax (on page 381).
Set the
Defa
ult Upper Critical Threshold for a specific sensor type:
config:# defaultThresholds <sensor type> upperCritical <value>
Set the Default Upper Warning Threshold for a specific sensor type:
config:# defaultThresholds <sensor type> upperWarning <value>
Set the Default Lower Critical Threshold for a specific sensor type:
config:# defaultThresholds <sensor type> lowerCritical <value>
Set the Default Lower Warning Threshold for a specific sensor type:
config:# defaultThresholds <sensor type> lowerWarning <value>
Set the Default Deassertion Hysteresis for a specific sensor type:
config:# defaultThresholds <sensor type> hysteresis <hy_value>
Set the Default Assertion Timeout for a specific sensor type:
config:# defaultThresholds <sensor type> assertionTimeout <as_value>
Variables:
<sensor type> is one of the following numeric sensor types:
Sensor types Description
absoluteHumidity Absolute humidity sensors
relativeHumidity Relative humidity sensors
temperature Temperature sensors
airPressure Air pressure sensors
airFlow Air flow sensors
vibration Vibration sensors
<value> is the value for the specified threshold of the specified sensor type. Note that diverse sensor
types use different measurement units.
Sensor types Measurement units
absoluteHumidity g/m^3 (that is, g/m
3
)