June 2018
Legrand PDU User Guide 339
Outlet Configuration Commands
An outlet configuration command begins with outlet. Such a command allows you to configure an individual
outlet.
Changing the Outlet Name
This command names an outlet.
config:# outlet <n> name "<name>"
Variables:
<n> is the number of the outlet that you want to configure.
<name> is a string comprising up to 64 ASCII printable characters. The <name> variable must be
enclosed in quotes when it contains spaces.
Changing an Outlet's Default State
This section applies to outlet-switching capable models only.
This command determines the initial power condition of an outlet after the Legrand PDU powers up.
config:# outlet <n> stateOnDeviceStartup <option>
Variables:
<n> is the number of the outlet that you want to configure.
<option> is one of the options: off, on, lastKnownState and pduDefined.
Option Description
off Turn off the outlet.
on Turn on the outlet.
lastKnownState Restore the outlet to the state prior to last PDU
power down.
pduDefined PDU-defined setting.
Note: Setting the outlet's default state to an option other than pduDefined overrides the PDU-defined default
state on that outlet. See Setting the PDU-Defined Default Outlet State (on page 295).