EasyManua.ls Logo

LEGRAND PDU - Miscellaneous

LEGRAND PDU
505 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
June 2018
Legrand PDU User Guide 229
To replace the current script, click Load Local File or Load Example to select a new script.
To delete a script:
1. Choose Device Settings > Lua Scripts.
2. Click the desired one in the scripts list.
3. Click
> Delete.
4. Click Delete on the confirmation message.
To return to the scripts list:
Click "Lua Scripts" on the top of the page.
Or click "Lua Scripts" in the Menu (on page 84).
Miscellaneous
By default, the Schroff LHX/SHX heat exchanger support and Cisco EnergyWise feature implemented on the
Legrand PDU are disabled.
However, Legrand PDU does NOT support Schroff LHX/SHX so you can ignore the checkbox for this device.
If a Cisco
®
EnergyWise energy management architecture is implemented in your place, you can enable the
Cisco EnergyWise endpoint implemented on the Legrand PDU so that this Legrand PDU becomes part of
the Cisco EnergyWise domain.
To set the Cisco EnergyWise configuration:
1. Choose Device Settings > Miscellaneous.
2. Select the Enable EnergyWise checkbox.
3. Configure the following:
Field Description
Domain name Type the name of a Cisco EnergyWise domain where
the Legrand PDU belongs
Up to 127 printable ASCII characters are permitted.
Spaces and asterisks are NOT acceptable.
Domain password Type the authentication password (secret) for entering
the Cisco EnergyWise domain
Up to 127 printable ASCII characters are permitted.
Spaces and asterisks are NOT acceptable.
Port Type a User Datagram Protocol (UDP) port number for
communications in the Cisco EnergyWise domain.
Range from 1 to 65535.
Default is 43440.
Polling interval Type a polling interval to determine how often the
Legrand PDU is queried in the Cisco EnergyWise
domain.
Range from 30 to 600 ms.
Default is 180 ms.
4. Click Save in the EnergyWise section.