Legrand PDU User Guide 375
Example 2 - Warning Thresholds for Inlet Sensors
The following command sets both the Upper Warning and Lower Warning thresholds for the inlet 1 RMS
current.
config:# sensor inlet 1 current upperWarning 20 lowerWarning 12
Results:
The Upper Warning threshold for the inlet 1 RMS current is set to 20A. It also enables the upper warning
threshold if this threshold has not been enabled yet.
The Lower Warning threshold for the inlet 1 RMS current is set to 12A. It also enables the lower warning
threshold if this threshold has not been enabled yet.
Example 3 - Upper Thresholds for Overcurrent Protector Sensors
The following command sets both the Upper Critical and Upper Warning thresholds for the 2nd overcurrent
protector.
config:# sensor ocp 2 current upperWarning enable upperCritical 16
Results:
The Upper Critical threshold for the 2nd overcurrent protector's RMS current is set to 16A. It also
enables the upper critical threshold if this threshold has not been enabled yet.
The Upper Warning threshold for the 2nd overcurrent protector's RMS current is enabled.