June 2018
Legrand PDU User Guide 95
For time-related fields, if you do not prefer the option selection using , you can type a value
manually which must include a time unit, such as '50 s'. See Time Units (on page 98).
In the following table, those
fields marked with * are available on an outlet-switching capable model
only.That is, Legrand Switched PDUs.
Field Function Note
Name Customizes the device name.
*Outlet state on
device startup
Determines the initial power state of
ALL outlets after the Legrand PDU
powers up.
Options: on, off, and last known
See Options for Outlet State on
Startup (on page 96).
After removing power from the
PDU, you must wait for a minimum
of 10 se
conds before powering it
up again. Otherwise, the default
outlet state settings may not work
properly.
You can override the global outlet
state setting on a per-outlet basis
so specific outlets behave
differently on startup. See
Individual Outlet Pages (on page
107).
*Outlet
initialization delay
on device startup
Determines how long the Legrand
PDU waits before providing power to
all outlets during power cycling or
after recovering from a temporary
power loss.
Range: 1 second to 1 hour
See Initialization Delay Use Cases
(on page 97).
*Power off period
during power cycle
Determines the power-off period after
the outlet is switched OFF during a
power cycle.
Range: 1 second to 1 hour
Power cycling the outlet(s) turns
the outlet(s) off and then back on.
You can override this global power
cycle setting on a per-outlet basis
so specific outlets' power-off
period is different. See Individual
Outlet Pages (on page 107).
*Inrush Guard
Delay
Prevents a circuit breaker trip due to
inrush current when many devices
connected to the PDU are turned on.
Range: 100 milliseconds to 10
seconds
See Inrush Current and Inrush
Guard Delay (on page 97).
Peripheral Device
Z Coordinate
Format
Determines how to describe the
vertical locations (Z coordinates) of
Raritan environmental sensor
packages.
Options: Rack-Units and
Free-Form
See Z Coordinate Format (on page
97).
To sp
ecify the location
of any
sensor/actuators in the data center,
see Individual Sensor/Actuator
Pages (on page 125).
Peripheral Device
Auto Management
Enables or disables the automatic
management feature for Raritan
environmental sensor packages.
The default is to enable it.
See How the Automatic
Management Function Works (on
page 98).