5.1.1
Tightening torques of the power terminals
Type
8601...8605
8606,8607
8608...8611
8612,8613 8614,8615
Tightening 0.6...0.8
Nm
1.2...1.5
Nm
1.5...1.8
Nm
6...8
Nm
15...20
Nm
torque (5.3...7.1
Ibfin)
(10.6...13.3
Ibfin)
(13.3...16
Ibfin)
(53,..70Ibfin)
(133...177 Ibfin)
5.2 Control connections
Layout:
,:T
EB
39
40
41
44 45
KIlK14Al
x3
x4
Xl
to x4: Control terminals
x5:
Input of digital
frequency/incremental
encoder
X6:
LECOM interface
(RS232/485)
X8: 2nd input of digital frequency/incremental encoder
(Option)
x9:
Output of digital frequency (Option)
Xl
0,
Xl
1:
Field bus connections
(Option, e.g.
2110lB
for
InterBus-S)
Vl,
v2;
Displays for field bus Options
Note
-
Always connect the plug-in terminals
(accessory
kit) to the plug
connectors
Xl
to X4.
When not using the interface plugs (plug-in connectors) X5 and X6
protect
them with the supplied
covers.
lt is possible to
Change
the
functions
of
cetiain
control terminals
using switches
(See
chapters
5.2.1 to 5.2.7, page 30ff). To
adjust
the switches, remove the
cover
of the device.
In addition to this, there are numerous possibilities to
Change
the
inputs and Outputs of the device using
Codes
(See
page
81ff).
-
29