6.5 Gable
protection
Cable protecting fuses for recommended
Cross-sections:
Controller type
8601
-
03
6604,05 6606,07
6606,OQ
Rated fuse current 16A
20 A 35 A
50A
Cable Cross-sectlon 2.5
mm*
4
mm2
10
mm2
16
mm2
AWG:3
(12)
AWG:i
(10)
AW::
(6)
AW:5
(4)
Controller type
6610,ll
6612 6613 6614 8615
Rated fuse current
63 A
IOOA
125A
160A
200 A
Cable
Cross-section
25
mm2
50
1171172
50
mm2
95
mm2
95
1171172
or
or or or or
AWG 3 AWGO AWG 0 AWG
310
AWG
310
Replace
defective
fuses only with the specified type and when the
device
is disconnected from the mains. All power terminals remain
live up to 3 minutes after mains disconnection!
Instead of
cable
protection fuses you
tan
also use miniature circuit
breakers (e.g. Siemens
type
5SX2,
3..
-
6)