6.4 Sine filter
Advantages of using a sine filter:
l Sinusoidal output voltages to supply
electronie
devices.
Please
note:
l Irrstall the sine filter as
close
as
possibie
to the controller.
l Select the control mode
“V/f-characteristic
control”
(COO6=-0-).
The “magnetizing-current control” form of control is
not permissibie.
l
The
chopper
frequency must be set to 8 kHz (CO1 8 = -4-).
L
The controller is loaded additionally with approximately 10% of
the rated current of the sine filter.
l The voltage drop
across
the sine filter at rated current and rated
frequency
(fd
= 50 Hz) is 7% of the Controller output voltage.
l The maximum permissible output frequency is 120 Hz.
l With unscreened motor cables it
shouid
be tested whether the
System
camplies
with the interference
Levels
required for the
CE-EMC conformity.
hze