5.2.6 Ramp generator stop
While the drive is accelerated via the ramp generator of the main
setpoint, you
tan
hold the ramp generator using the assigned
digital input,
e.g.
to wait for cet-tain
actions
before accelerating.
With terminal control you
tan
read
under
Cl31
whether the
ramp generator is stopped or not.
With control via the keypad or the LECOM interfaces the ramp
generator (main setpoint) is stopped and enabled again
under
C131.
Code Name
Parameter
(Factory setting is printed in bold)
Acceptance
Cl31
Ramp gener.
-O- Enable
ramp generator SH + PRG
stop
-l-
Stop ramp generator
5.2.7 Ramp generator input =
0
If
you want to stop the drive independently of the main
setpoint
(setpoint
i/JOG
frequency) you
tan
switch
the ramp generator
input input to zero using the assigned input. This
Causes
the drive
to brake with the set deceleration time. When the
function
is
deactivated, the main
setpoint
is enabled again and the drive
accelerates normally.
With terminal control
Cl32
serves as display whether the ramp
generator input is set to zero or not.
With control via keypad or LECOM interfaces you
tan
set the ramp
generator to zero and enable it again
under
Cl 32.
Code Name
Parameter (Factory setting is printed in bold) Acceptance
Cl32
Ramp-
-o- Ramp generator input enabled
SH
+
PRG
generator input
-l-
Ramp generator input =
O/
=
0
set to zero
5.2.8 Integral action component =
0
In configurations with Pl controller you
tan
set the integral action
component of the controller to zero using the assigned input. See
page 80.
-