l Calculate the required act. value gain according to the following
equation:
Required gain =
active
gain
measured
Speed
desired
Speed
l Enter the calculated value after selecting the suitable act. value
input (C025)
under
C027.
--
4.5
Setting of the controller Parameters
With the setting of the Controller Parameters, you adapt the Pl
Controller to the drive. This adjustment is
necessary
after the
auto-
adjustment as well as after the manual adjustment. Proceed as
follows:
l Increase the gain of the Pl controller
under
Code
CO70 until the
drrve
stark
to oscillate.
l Then reduce this value by 10%.
l If there should be no
oscillation
with a gain of 10, reduce the
adjustment time
under
CO71,
until the drive stark to oscillate.
l Then reduce the gain by 10%.
l If
,the
System
already oscillates with the factory setting, increase
the adjustment time, until the drive runs smoothly.
Code Name Parameter
(Factory
setting is printed in bold) Acceptance
CO70 Gain of
1 .oo 0.01
(0.01)
1
.OO
ON-LINE
PI controller 1 .o
lO.11
10.0
10
Ul
300
CO71
Adjustment
0.10 s 0.01 s
(0.01)
1
.OO
s ON-LINE
time of 1.0 s
Oll
10.0s
Pl
controlller
10s
(11
100s
lmze
79