Moulded module resistors on heatsink
I
,
,k-i
I
d
b
Brake resistor
Dimensions
Resistance Order number
a
b
C
d e
Cl
k
a
mm
mm
mm mm mm mm
mm
370
ERBM370R15OW 80
240 70 225 95
5
7.5
240
ERBM240R200W 80
340 70 325 70 5 7.5
Brake resistor
Resistance Order number
n
370
ERBM370R15OW
240
ERBM240R200W
Power
kW
0.15
0.2
Resistor values
Peak brake power
kW
1.4
2.2
Heat capacitance
kWs
30
30
6.2
Mains
Chokes
Advantages of using a mains
Choke:
l Less mains disturbance
The wave shape of the mains current
approaches
sinusoidal; at
the same time the
r.m.s.
current is reduced by up to 40%
(reduction
of the mains load, the
cable
load and the fuse load).
l Increased life of the Controller
A mains
Choke
reduces
the AC load of the DC bus capacitors
and thus doubles its Service life.
l The transient high-energy overvoltages
which
are sometimes
generated at the mains side by circuit breakers or fuses are
stopped by the mains
Choke
and thus the units are usually not
damaged.
l Low-frequent radio interference
tan
be reduced.
Please note:
l When a mains
Choke
is used, the maximum possible output
voltage does not
resch
the value of the mains voltage.
-
typicat voltage drop at the rated
Point:
4 to 5%.
l Mains
Chokes
are always required when the Controller is
operated with increased or maximum power.
-
42