L-DALI User Manual 345 LOYTEC
Version 5.2 LOYTEC electronics GmbH
8.3.5.9 Interaction with other BACnet Objects
The Loop Object allows automatically retrieving its input values from and writing its output
values to other BACnet server objects. To reference the property and server object it
provides properties of type BACnetObjectPropertyReference. Specifically these are:
Manipulated_Variable_Reference: Writing Present_Value (Constant Light Controller
output, e.g. to Analog Output controlling DALI lights, see Section 8.3.3.10).
Controlled_Variable_Reference: Reading lux level input (e.g. from DALI lux level
sensor, see Section 8.3.4.2).
Setpoint_Reference: Reading setpoint value.
Occupancy_Variable_Reference (property ID 537): Reading occupancy input (e.g.
from DALI occupancy sensor, see Section 8.3.4.3).
Note, that the referenced server object must be local.
Alternatively internal bindings can be configured as described in Section 5.3.2.
8.3.5.10 Loop Object – Constant Light Controller application
This object is used to represent a constant light controller instance (see Table 40). There are
up to 16 instances per DALI channel available.