5-18
Application Manual CDA3000
5 Software functions
Configuration options, ISA0x
Parameters for analog inputs ISA0x
Figure 5.5 Scaling in unipolar
operation
Figure 5.6 Backlash function in
bipolar operation
f
U/I
-10 V
+10 V
+f
max
0-10V
0-20mA
-f
max
-f
min
FxPNy
FxPXy
+f
min
f
-10 V
+10 V
U/I
+f
max
-f
max
IADBx
FxNNy
FxPNy
FxPXy
FxNXy
IADBx
Parameter Function Value range FS Unit Online
180-FISA0 Function selector analog standard input
ISA00
see Table 5.11 OFF
181-FISA1 Function selector analog standard input
ISA01
see Table 5.11 OFF
182-F0PX1 CDS1: Maximum value ISA00 at +10V -1600 ... 1600 50 Hz
183-F0PN1 CDS1: Minimum value ISA00 at +0V -1600 ... 1600 0 Hz
184-F0NX1 CDS1: Maximum value ISA00 at -10V -1600 ... 1600 0 Hz
185-F0NN1 CDS1: Minimum value ISA00 at -0V -1600 ... 1600 0 Hz
186-F1PX1 CDS1: Maximum value ISA01 at +10V -1600 ... 1600 50 Hz
187-F1PN1 CDS1: Minimum value ISA01 at +0V -1600 ... 1600 0 Hz
188-AFIL0 Filter time constant for analog channel ISA00
(2
x
), x = 0 ... 6
3
189-AFIL1 Filter time constant for analog channel ISA01
(2
x
), x = 0 ... 6
3
190-F0PX2 CDS2: Maximum value ISA00 at +10V -1600 ... 1600 50 Hz
191-F0PN2 CDS2: Minimum value ISA00 at +0V -1600 ... 1600 0 Hz
194-F0NX2 CDS2: Maximum value ISA00 at -10V -1600 ... 1600 0 Hz
195-F0NN2 CDS2: Minimum value ISA00 at -0V -1600 ... 1600 0 Hz
196-F1PX2 CDS2: Maximum value ISA01 at +10V -1600 ... 1600 50 Hz
197-F1PN2 CDS2: Minimum value ISA01 at +0V -1600 ... 1600 0 Hz
192-IADB0 ISA00 play range
0 ... 90 0.00
%
1)
193-IADB1 ISA01 play range
0 ... 90 0.00
%
1)
1)
Referred to 10 V
Table 5.10 Parameters from subject area _18IA-Analog inputs