Application Manual CDA3000
5-19
5  Software functions
1
2
3
4
5
6
A
DE
EN
FR
Settings for 180-FISA0 and 181-FISA1 analog inputs
BUS KP/DM Function Effect
0 OFF No function Input off
1 STR Start clockwise Start enable for motor clockwise running
2 STL Start anti-clockwise Start enable for motor anti-clockwise running
3 INV Reverse direction Reference is inverted, causing a reversal of 
direction
4 /STOP /Emergency stop Stop ramp is executed dependent on active 
characteristic data set (CDS).
Attention: Signal inverted ( / )
(section 5.5.3 “_59 DP-Driving profile genera-
tor”)
5 SADD1 Offset for reference 
selector 280 -RSSL1
Reference selector 280-RSSL1 is offset by the 
value in 289-SADD1 to a different reference 
source (section 5.2.6 “_28 RS-Reference struc-
ture”).
6 SADD2 Offset for reference 
selector 281 -RSSL2
Reference selector 281-RSSL2 is offset by the 
value in 290-SADD2 to a different reference 
source (section 5.2.6 “_28 RS-Reference struc-
ture”).
7 E-EXT External error Error messages from external devices produce a 
fault signal with response as defined in parame-
ter 524-R-EXT (section 5.3.10 “_51ER-Error 
messages”).
8 RSERR Reset error message Error messages are reset if the error is no longer 
present.
9 MP-UP MOP, increase refer-
ence value
The reference value of the digital MOP function 
is increased (section 5.5.2 “_32 MP-MOP 
function”).
10 MP-DN MOP, reduce refer-
ence value
The reference value of the digital MOP function 
is reduced (section 5.5.2 “_32 MP-MOP 
function”).
11 CUSEL Select characteristic 
data set (CDS)
Switch characteristic data set (CDS)
0 = CDS1, 1 = CDS2
(section 5.5.6 “_65 CS-Characteristic data swit-
chover (CDS)”).
12 FFTB0 Driving set selection
(significance 2
0
)
Binary driving set selection (bit 0), frequency 
with acceleration and deceleration ramp (section 
5.5.5 “_60 TB-Driving sets”).
13 FFTB1 Driving set selection 
(significance 2
1
)
Binary driving set selection (bit 1), fixed fre-
quency with acceleration and deceleration ramp 
(section 5.5.5 “_60 TB-Driving sets”).
Table 5.11 Settings for analog inputs