Application Manual CDA3000
5-29
5 Software functions
1
2
3
4
5
6
A
DE
EN
FR
6 SADD2 Offset for reference selector 281-
RSSL2
Reference selector 281-RSSL2 is offset by
the value in 290-SADD2 to a different refer-
ence source.
(section 5.2.6 “_28 RS-Reference struc-
ture”)
7 E-EXT External error in another device Error messages from external devices pro-
duce a fault signal with response as defined
in parameter 524-R-EXT.
(section 5.3.10 “_51ER-Error messages”)
8 RSERR Reset error message Error messages are reset if the error is no
longer present.
9 MP-UP MOP, increase reference value Reference value of digital MOP function is
increased.
(section 5.5.2 “_32 MP-MOP function”)
10 MP-DN MOP, reduce reference value Reference value of digital MOP function is
reduced.
(section 5.5.2 “_32 MP-MOP function”)
11 CUSEL Select characteristic data set (CDS) Switch characteristic data set (CDS)
0 = CDS1, 1 = CDS2
(section 5.5.6 “_65 CS-Characteristic data
switchover (CDS)”)
12 FFTB0
Driving set selection (significance 2
0
)
Binary driving set selection (bit 0), fixed fre-
quency with acceleration and deceleration
ramp.
(section 5.5.5 “_60 TB-Driving sets”)
13 FFTB1
Driving set selection (significance 2
1
)
Binary driving set selection (bit 1), fixed fre-
quency with acceleration and deceleration
ramp.
(section 5.5.5 “_60 TB-Driving sets”)
14 FFTB2
Driving set selection (significance 2
2
)
Binary driving set selection (bit 2), fixed fre-
quency with acceleration and deceleration
ramp.
(section 5.5.5 “_60 TB-Driving sets”)
15 UM0 User data set (UDS) switchover, (signifi-
cance 2
0
)
Binary data set selection (bit 0)
(section 5.1 “_15 FC-Initial commission-
ing”)
BUS KP/ DM Function Effect
F
I
S
0
0
F
I
S
0
1
F
I
S
0
2
F
I
S
0
3
F
I
E
0
x
F
I
F
x
Table 5.17 Settings of the function selectors