5-98
Application Manual CDA3000
5  Software functions
For this, a minimum phase current is monitored sequentially in all three
phases. If the minimum current is registered once in all phases, the hol-
ding brake is actuated and the drive thus enabled. There is no continuous
monitoring of the motor current.
Inverter module Inverter output power [kW]
Detected I
min
 [A]
CDA32003 0.375 0.23
CDA32004 0.75 0.38
CDA32006 1.1 0.51
CDA32008 1.5 0.66
CDA34003 0.75 0.21
CDA34005 1.5 0.37
CDA34006 2.2 0.53
CDA34008 3.0 0.72
CDA34010 4.0 0.94
CDA34014 5.5 1.29
CDA34017 7.5 1.58
CDA34024 11 2.16
CDA34032 15 2.83
CDA34045 22 3.00
CDA34060 30 4.00
CDA34072 37 4.96
CDA34090 45 6.11
CDA34110 55 7.07
CDA34143 75 9.44
CDA34170 90 12.01
Table 5.59 Current threshold for detection of current application to motor