6-10
Application Manual CDA3000
6 Control modes
Settings of assistance parameters 730-ASCA1 and 731 -ASCA2
The parameters ASCU contain preset characteristic shapes based on the
setting options of the six interpolation points of the V/F characteristic.
Explanatory notes
The values marked with an asterisk (*) are dependent on device
version 230 V or 400 V.
CDS1 = Characteristic data set 1, CDS2 = Characteristic data set 2
The voltages between two interpolation points are interpolated in
linear mode.
Interpolation points with the setting 0 Hz are inactive.
The sequence of interpolation points is automatically sorted in
ascending order of frequency. As a result, a new interpolation point
can also be entered without having to shift other interpolation point
settings.
During controller initialization the limit values of the settings are
checked. If the limit values are infringed an error message is deliv-
ered (see Appendix).
BUS KP/DM Function Usage
0 OFF
Fully programmable characteristic with up to six
interpolation points
Optimum setting options for V/F control of
special motors
1 L50Hz
Linear 50 Hz characteristic with two interpolation
points
Standard motor (European market)
2 L60Hz
Linear 60 Hz characteristic with two interpolation
points
Standard motor (American market)
3 L87Hz
Linear 87 Hz characteristic with two interpolation
points
Expanded manipulating range for
4 Q50Hz
Quadratic 50 Hz characteristic with six interpolation
points
Standard motor (European market) for pump
and fan applications
5 Q60Hz
Quadratic 60 Hz characteristic with six interpolation
points
Standard motor (American market) for pump
and fan applications
Table 6.4 Setting of predefined V/F characteristics