Application Manual CDA3000
A-15
Appendix B Error messages
1
2
3
4
5
6
A
DE
EN
FR
5 E-OLM
1
Ixt shut-off to protect motor (permissible
current/time area exceeded once/more than
once)
1. Reduce load; 2. Use higher-pow-
ered Motor
LOCK
6 E-OLI
1
I^2xt shut-off to protect power stage
(permissible current/time area exceeded
once/more than once)
Reduce load. LOCK
7 E-OTM
18
Motor overheating (PTC in motor tripped)
due to: 1. PTC not connected; 2. Motor
overload
1. Allow motor to cool down; 2. Con-
nect PTC or jumper terminals with
100 Ohms; 3. Use a higher-powered
motor
LOCK
8 E-OTI
31
Power stage overheating due to: 1. ambient
temperature too high; 2. load too high
(power stage or braking chopper)
1. Improve ventilation; 2. Use higher-
powered device
LOCK
32
Overheating in device interior due to:
1. ambient temperature too high; 2. load too
high (power stage or braking chopper)
1. Improve ventilation; 2. Use higher-
powered device
Bus DM/KP
Error
location
no.
Error cause Possible remedy
Response
no.
in FS
(1) If this error is repeated please contact your local Service Partner.
Table A.2 Error messages of the CDA3000