A-16
Application Manual CDA3000
Appendix B Error messages
9 E-PLS
1
Plausibility check detected invalid parameter
or impermissible program sequence
(1) RESET
6
Unknown switching frequency in initializa-
tion of power stage protection
(1)
8
Parameter list could not be initialized in
device startup phase. KP200 indicates
number of incorrect parameter when appro-
priate at top left of display.
Reset device by: 1. Set parameter
PROG=1. 2. Switch off device, press
and hold down Up and Down key on
KP200 and switch device back on.
KP200 indicates “RESET”
9
Plausibility check detected invalid parameter
object (incorrect data type or data length)
(1)
10
No readable parameter exists at the current
user level or parameter access error via
KP200
(1)
13 Both slots assigned the same module Remove one module.
20
Error in auto-tuning 1. Check motor rating plate data
matches corresponding motor param-
eters and restart auto-tuning. 2. (1)
101
Unknown switching frequency in initializa-
tion of PWM
(1)
Bus DM/KP
Error
location
no.
Error cause Possible remedy
Response
no.
in FS
(1) If this error is repeated please contact your local Service Partner.
Table A.2 Error messages of the CDA3000