EasyManua.ls Logo

Lust CDA3000 - Page 333

Lust CDA3000
358 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Application Manual CDA3000
A-17
Appendix B Error messages
1
2
3
4
5
6
A
DE
EN
FR
10 E-PAR
0
Invalid parameter setting Correct parameter setting or reset
device to factory setting.
RESET
2
Parameter FMINx greater than parameter
FMAXx or error in initialization of current-
controlled startup
Set FMINx < FMAXx
7
The value of a parameter after the device
startup phase is outside its value range.
Parameter 423-ERPAR contains the
number of the incorrect parameter
whose setting needs to be checked.
8
Error in first initialization of parameter list.
A parameter could not be set to the factory
setting.
Parameter 423-ERPAR contains the
number of the incorrect parameter
whose setting needs to be checked.
13
The combination of function selector set-
tings for one of the analog inputs and the
reference selector are mutually contradic-
tory.
Check and change setting.
16
The setting of parameter FOSA0 (function
selector, output OSA0) is outside its value
range.
Check and change setting.
100
Error in controller initialization Check setting of controller and motor
parameters. Restart auto-tuning as
necessary.
101 Error in initialization of PWM (1)
102 Error in initialization of encoder evaluation (1)
104
Error in initialization of Voltage Frequency
Control
(1)
105
Error in initialization of actual value record-
ing
(1)
106
Two interpolation points of V/F characteristic
have same frequency.
Change setting.
107
Pitch between two interpolation points for
V/F characteristic is too large.
Change setting.
108
Error in initialization of SFC resulting from
unfavourable parameter settings of motor
and controller.
Check controller and motor settings
and restart auto-tuning as necessary.
11 E-FLT 0 Global error in floating point calculation (1) RESET
Bus DM/KP
Error
location
no.
Error cause Possible remedy
Response
no.
in FS
(1) If this error is repeated please contact your local Service Partner.
Table A.2 Error messages of the CDA3000