A-18
Application Manual CDA3000
Appendix B Error messages
12 E-PWR 6 Power pack not correctly detected Send in device . RESET
13 E-EXT 1 Error in an external device Rectify error in external device. STOP
15 E-OP1 150 Error in module at option slot 1 1. Check module and identifier; 2. (1) STOP
151
Error at option slot 2: BUS-OFF state
detected
Check contacting of module. If the
error reoccurs after switching on/off,
the device or the module is faulty.
152
Error at option slot 2: Transmit protocol
could not be sent.
Check contacting of module. If the
error reoccurs after switching on/off,
the device or the module is faulty.
153
Error at option slot 2: Module not responding Check contacting of module. If the
error reoccurs after switching on/off,
the device or the module is faulty.
154
Error at option slot 2: Module has signalled
error.
Check contacting of module. If the
error reoccurs after switching on/off,
the device or the module is faulty.
16 E-OP2 200 Error in module at option slot 2 1. Check module and identifier; 2. (1) STOP
201
Error on option 2: BUS-OFF state detected Check contacting of module. If the
error reoccurs after switching on/off,
the device or the module is faulty.
202
Error on option 2: Transmit protocol could
not be sent.
Check contacting of module. If the
error reoccurs after switching on/off,
the device or the module is faulty.
203
Error on option 2: Module not responding Check contacting of module. If the
error reoccurs after switching on/off,
the device or the module is faulty.
204
Error on option 2: Module has signalled
error.
Check contacting of module. If the
error reoccurs after switching on/off,
the device or the module is faulty.
18 E-SIO
11
Watchdog monitoring communication over
LustBus tripped
1. Check connection; 2. Check bus
master or increase parameter SWDGT.
STOP
19 E-EEP 3 Error accessing parameter memory 1. Switch device off and back on; 2.(1) RESET
20 E-WBK
1
Possible wire break at input ISA01.
Current less than 4mA in parameter setting
to 4-20mA
Check wiring of input ISA01. STOP
Bus DM/KP
Error
location
no.
Error cause Possible remedy
Response
no.
in FS
(1) If this error is repeated please contact your local Service Partner.
Table A.2 Error messages of the CDA3000