4-18
Application Manual CDA3000
4 Application data sets
Note: After parameter setting of the user data sets the parameter
value 166-UDSSL must be changed from PARAM (K
EYPAD,
D
RIVEMANAGER) to TERM (terminal operation) and saved
accordingly (see section 5.1 _15 FC-Initial commissioning).
The parameter presets for application data sets DRV_x are located as
parameter comparison references in section 4.3.6 Comparison of para-
meters, traction and lifting drive.
Attention: When control mode FOR is changed to VFC in parameter
300-CFCON, it is essential that the response to reference 0
Hz in parameter 597-RF0 should be set to OFF, otherwise
current will be continuously applied to the motor in uncontrol-
led mode while at standstill. This may result in the motor
overheating.
Encoder A HTL encoder (see Figure 4.12) can be connected to terminals X2:11
and X2:12.
Figure 4.12 Block diagram, HTL output circuit