Application Manual CDA3000
4-21
4  Application data sets
1
2
3
4
5
6
A
DE
EN
FR
Control terminals of user module UM-8I4O
Figure 4.15 Assignment of control terminal expansion with ASTER = DRV_5
Note: If limit switch evaluation is not required, the 24 V auxiliary
voltage (UV) should be jumpered from terminal X15:21
directly to terminals X15:26 and X15:27 of the limit switch
inputs. As an alternative, both digital inputs can also be deac-
tivated with function selectors 218-FIE04 and 219-FIE05
respectively, or be assigned a different function (see section
5.2.3).
Note: After parameter setting of the user data sets the parameter
value 166-UDSSL must be changed from PARAM (K
EYPAD,
D
RIVEMANAGER) to TERM (terminal operation) and saved
accordingly (see section 5.1 “_15 FC-Initial commissioning”).
34
5
67 8910
11 12
1
2
16
17 18
19 20
X15
H1 H2 H3
X4
X2
X1
X3
ANTRIEBSTECHNIK
D-35633 Lahnau
L3
U
V
W
RB+
RB
L-
L1
L2
12
345
16 17 18 19 20
11 12 13 14 15
678
910
ACHTUNG
Kondensatorent-
ladezeit >3 Min.
Betriebsanleitung
beachten!
WARNING
capacitor disscharge
time >3 minutes.
Pay attention to the
operation manual!
ATTENTION
temps de decharge
du condensteur
>3 min. observer le
mode dèmploi!
!
OPTN1 (X6)
X1  Des. Function
1 U
V
24 V supply +20%, 0.6 A
2 DGND Digital ground
21
U
V
Auxiliary voltage 24 V
22 IED00 Switch to driving sets
23 IED01
Select driving sets for fixed frequencies 
(section 5.5.5 _60TB Driving sets)
24 IED02
25 IED03
26 IED04 Limit switch right
27 IED05 Limit switch left
28 IED06
User data set switchover
29 IED07
30 DGND Digital ground
31 DGND Digital ground
32 OED00 Warning “Inverter module overloaded”
33 OED01 Warning “Motor overloaded”
34 OED02
Warning “80% of I
N
 exceeded”
35 OED03 Warning “Ambient temperature too high”
S8
H5
H4
H3
H2
S6
S5
S7
S3
S4
S2
S1