If applicable, press the [No] softkey to keep the original values.
3. Enter and conrm e.g.the value for 4 mA measured by the connected PLC under
[Measured].
The window for the 2nd value opens.
4. Enter and conrm e.g.the value for 20 mA measured by the connected PLC under
[Measured].
A prompt window opens.
5. Press the [Yes] softkey to save the settings.
The following window opens: