432
APPENDICES
Appendix 4 Special Registers
SD10 Self-diagnostic error
code
Self-diagnostic error code 1 The maximum of 16 types of error codes are stored into SD10 onwards
when the diagnostics detects an error.
(The same error code as one already stored in SD10 onwards is not
stored). The 17th error code onwards are not stored. Also error codes
are not stored when 16 types of error codes have already been stored
into SD10 to SD25.
S (Error)
SD11 Self-diagnostic error code 2
SD12 Self-diagnostic error code 3
SD13 Self-diagnostic error code 4
SD14 Self-diagnostic error code 5
SD15 Self-diagnostic error code 6
SD16 Self-diagnostic error code 7
SD17 Self-diagnostic error code 8
SD18 Self-diagnostic error code 9
SD19 Self-diagnostic error code
10
SD20 Self-diagnostic error code 11
SD21 Self-diagnostic error code
12
SD22 Self-diagnostic error code
13
SD23 Self-diagnostic error code
14
SD24 Self-diagnostic error code
15
SD25 Self-diagnostic error code
16
SD53 AC/DC DOWN
detection
Number of times for AC/DC
DOWN detection
• Every time the input voltage fails to or below (85[%] AC power/65[%]
DC power) the rating during calculation of the Motion CPU module, the
value is incremented by 1 and stored in BIN code.
• The counter repeats a 0 to 65535 to 0 pattern.
SD61 I/O module verify
error module number
I/O module verify error
module number
The lowest I/O number of the module which has an error detected by the
I/O module verification is stored.
SD80 Detailed information
1 information
category
Detailed information 1
information category code
• Detailed information 1 information category code is stored.
• The following codes are stored into the information category code.
0: N/A
1: Program position information
2: Drive and file information
4: Parameter information
5: System configuration information
6: Number of times information
7: Time information
129: G-code control information
131: Machine control information
135: Add-on function information
141: Servo error/error at communication failure
142: Axis control error
143: Motion SFC program
No. Name Data stored Details Set by
(setting
timing)
b15 b8 b7 b0
Not used (fixed to 0)
to
Information block code
to