9-44 Manual # 42-02-2223
Reference
PowerBack R6 Regenerative Drive Quick Reference
This section includes quick reference information for the PowerBack R6 Regenerative AC drive.
Please refer to the R6 Regenerative drive manual provided with the iControl for detailed expla-
nation of the parameters.
Table 9.6 Quick Reference for PowerBack R6 Regenerative Drive
WARNING: Do not change drive parameters while the elevator is running. Incorrect values of
drive parameters can cause erratic elevator operation.
Display Parameter Description Setting Range Resolution
Field/MCE Set
ting
CP. 0 Password input 0...9999 1 ---
CP. 1 Status display --- --- ---
CP. 2 Main Line Frequency --- 0.1 Hz ---
CP. 3 AC-Phase current L1 --- 0.1 A ---
CP. 4 AC-Phase current L2 --- 0.1 A ---
CP. 5 AC-Phase current L3 --- 0.1 A ---
CP. 6 Actual Load --- 1% ---
CP. 7 Actual Load / peak value --- 1% ---
CP. 8 DC output current --- 0.1 A ---
CP. 9 Actual DC voltage --- 1 V ---
CP.10 DC voltage / peak value --- 1 V ---
CP.11 Heat sink temperature ---
1
0
C
---
CP.12 Over load counter --- 1% ---
CP.13 Active power --- 0.1kW ---
CP.14 Total regen kWhr counter --- 0.1 kWh ---
CP.15 Total motor kWhr counter --- 0.1 kWh ---
CP.16 Total net kWhr counter --- 0.1 kWh ---
CP.17 Apparent power / Line input --- 0.1 kVA ---
CP.18 Analog output 1 / amplification factor -20.00...20.00 0.01 1.00
CP.19 DC bus switching level +/- 30000.00 0.01
Set to 260 for 208 - 240Vac
Set to 600 for 460 - 480Vac
CP.20 Auto error reset counter 0...10 1 3
CP.21 Last Error --- ---
CP.22 Last Error 1 --- ---
CP.23 Last Error 2 --- ---
CP.24 Last Error 3 --- ---
CP.25 Last Error 4 --- ---
CP.26 Last Error 5 --- ---
CP.27 Last Error 6 --- ---
CP.28 Last Error 7 --- ---
CP.29 Software version ---
CP.30 Software date code DDMM.Y
CP.31 Power part ID code ---
Set to 250 for 208 - 240Vac
Set to 253 for 460 - 480Vac
CP.32* Pulse off Level -100kW...0.0kW 0.1kW -0.8kW
CP.33*
Operating Mode
0: Master with Commutation Choke
2: Slave with Commutation Choke
0...3 1
Set to 0 for Main Regen drive
Set to 2 for Second drive
CP.34* Control Angle 0.0...60.0 0.1 29.0
*NEW PARAMETERS in software version 1.3
Job #: Drive Serial #:
Production Order # Test Technician:
Drive Model #: Date: