Chapter 12: Cooling Fans
No Fan 3
Prevents Fan 3 alarm (and associated LED) when no fan 3 is configured.
12.2.3
Airflow
MTS LiTE:
The card cage has a clear opening in the bottom front and small holes in the side and back. Ambient
airflow enters at the bottom of the front, back and sides and passes up through the modules. The
optimal solution is to allow the air inlet from all sides. At the top of the card cage there is enough space
for the air to distribute and spread before passing out of the venting grill at the top. If there is nothing in
close area to sides, the air can also exit here. The airflow routing is the same with or without fans.
Figure 186: MTS LiTE Airflow
MTS 2:
The 2 BR card cage has a clear opening in the bottom front and small holes in the side and back.
Ambient airflow enters at the bottom of the front, back and sides and passes up through the modules.
The optimal solution is to allow the air inlet from all sides. At the top of the card cage there is enough
space for the air to distribute and spread. It then passes up through the filter section and out of the
venting grill at the top. If there is nothing in close area to sides, the air can also exit here. The airflow
routing is the same with or without fans.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Motorola DIMETRA X Core and is the answer not in the manual?

Motorola DIMETRA X Core Specifications

General IconGeneral
BrandMotorola
ModelDIMETRA X Core
CategoryAccessories
LanguageEnglish

Related product manuals