NMC-PRO Installation Manual
73Page
PROGRAM MENU
Note: If more than one cooling valve is def
i
ned, the off time will take place after the last valve in the sequence
(Cooling valve #2, in the above screen). Between the cooling valves there is no delay and they are working in
sequence, from the first valve on the left side to the last one.
Note: If the time is relevant only for a certain period, only its settings will define operation. If humidity is above the
lowest value of the two periods, cooling will not take place.
From (hh:mm): Set the start time of the Cooling / Humidification program.
To (hh:mm): Set the end time of the Cooling / Humidification program
Note: The program will only be operational in the defined time window (between start “From” to end “To” times).
Each program can be operational on different hours.
Above t
o
/ Below RH
Above t
o
(when status is cooling): Start cooling above this temperature. Cooling will stop if the
temperature drops below the internal dead-band of 0.5
o
C. For example if set to 30
o
C cooling will start
when the temperature is above 30
o
C and will stop when it drops below 29.5
o
C. °
Below RH (when status is humidification): Start humidification below this humidity. Humidification will
stop if the humidity goes above the internal dead-band of 1%. For example, if set to 80% humidification
will start when the humidity is below 80% and will stop when it is above 81%.
Below RH / Above t
o
Below RH (when status is cooling): Stop cooling above this humidity. Cooling will be resumed when
the humidity drops below the internal dead-band of 2%. For example, if set to 80% cooling will stop
when the humidity is above 82% and will be resumed when the humidity drops below 80%.
Above t
o
(when status is humidification): Stop humidification when the temperature is below this
temperature. Humidification will be resumed when the temperature goes above the internal dead-band
of 0.5
o
C. For example, if set to 25
o
C humidification will stop when the temperature drops below 24.5
o
C
and will be resumed when it goes above 25
o
C.
On (hh:mm:ss): Define the On time of the Cooling valve. If On time is set to zero the Cooling valve will not be
opened.
Off (hh:mm:ss): Define the Off time of the Cooling valve. If Off time is set to zero the Cooling valve will be
constantly On.
Cool #: Assign cooling valves to this program. The assigned cooling valves will be operated sequentially in
groups. The number of groups (different cooling programs) which can be operated simultaneously (maximum
cooling parallel) is defined in screen 6.2 SYSTEM SETUP
.
Temp. Sens.: Assign Up to two temperature sensors for this program.
Hum. Sens.: Assign up to two humidity sensor to this program.

Table of Contents

Other manuals for Netafim nmc-pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Netafim nmc-pro and is the answer not in the manual?

Netafim nmc-pro Specifications

General IconGeneral
BrandNetafim
Modelnmc-pro
CategoryController
LanguageEnglish

Related product manuals