EasyManua.ls Logo

Netafim nmc-pro - Analog Output Test

Netafim nmc-pro
167 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NMC-PRO Installation Manual
96Page
TEST MENU
9.7 Analog Output Test
The Analog Output test screen enables testing the valves' opening, both while in operation or off-line. The test shows:
The amount of current going to the valve
Test results
From these data points, the user can troubleshoot a faulty valve.
Define and map the analog output card(s) in Analog Output, page 129.
Configure dosing in Dosing Configuration, page 119.
To test the analog output valves:
Under Status, select one of the following:
AUTO: PRO Irrigation tests the valve opening percentage. Use this option while the controller is
operating.
MAN: The user defines the valves' opening percentage.
The screen displays the test results:
Meas: This field displays the amperage used to open the valve, from 4 - 20 mA. 4 corresponds to
closed completely (0%) and 20 corresponds to open completely (100%).
Fail:
o ON: The valve is not operating properly
o OFF: The valve is operating properly
Troubleshooting:
If the test fails and there is high amperage, the card is installed improperly (Number 1 in the above
figure).
If the test fails and there is no amperage (4.00), there is a short circuit (Number 2 in the above figure).
ANALOG OUTPUT
N#
Status
Open%
Meas
Fail
1
AUTO
70
54.00
ON
2
AUTO
70
4.00
ON
3
MAN
50
10.50
OFF
4
MAN
70
14.00
OFF
5
AUTO
60
12.00
OFF
6
AUTO
60
12.00
OFF
7
AUTO
60
12.00
OFF
8
AUTO
60
12.00
OFF

Table of Contents

Other manuals for Netafim nmc-pro

Related product manuals